TSBSB Shock Relay series – Overload protection has built-in reset button, test button, fail-safe contacts with manual and automatic reset feature
    TSBSB Shock Relay senses the problem before downtime, maintenance, and equipment damage occur, saving you time and money. Install it on a line, set the overload parameters, and Shock Relay takes care of the rest. If an overload is detected, the Shock Relay can send a warning or shut down the line – quick and reliably. Correct the problem and you’re up and running again in minutes.
Unit of Measure

Specifications

Transformer

N/A TSB2CT200

Motor HP 230 VAC

N/A 30 to 50 hp

Motor HP 460 VAC

N/A 70 to 120 hp

Operation Power

N/A 24 to 240 V AC/DC +/- 10%, 50/60 Hz

Maximum Motor Voltage

N/A 600 VAC at 50/60 Hz

Load Current Setting Range

N/A 20 to 200 A

Trip Output Relay Status - Energized/Fail Safe to Open

N/A Manual Setting

Trip Output Relay Status - Energized/Fail Safe Close

N/A Automatic Setting

Trip Output Relay Contact Rating

N/A 3A Load

Start Time Setting Range

N/A 0.2 to 10 arc·sec

Shock Time Setting Range

N/A 0.2 to 5 arc·sec

Allow. Input Voltage Fluctuation (Full Scale)

N/A 10 %
Output Contact1 N/A 3A/250 VAC, Resistive

Test Button

N/A Yes

Test Function

N/A Built In

Withstanding Voltage

N/A 2000 VAC, 5 mA at 60 Hz for 1 min. between terminal and enclosure

Weight

N/A 1.540 lb0.70 kg

Shock Relay Power Supply

N/A 90 to 240 VAC

Power Consumption (or less)

N/A 2 W

Operating Temperature Range

N/A -4 to 140 ºF-20 to 60 ºC

Max. Elevation

N/A 2000 m6500 ft

Operating Humidity

N/A 45 to 85% R.H. with no condensation

Atmosphere

N/A Free of corrosive gas and dust. Pollution degree 3 or below when installed in control box

Protection Rating

N/A IP20

Construction Material

N/A Material Lower Housing - PA66 Material Upper Housing - PA6 Terminal Cover - PA6

Certifications

N/A CCC - China CE Marking - Europe RoHS Compliant UL/cUL - North America

Mounting

N/A 35 mm DIN Rail or Mounting Plate

Storage Temperature Range

N/A -22 to 158 ºF-30 to 70 ºC
  • 1 If the starter coil in the magnetic contactor (MC) of the monitored motor exceeds the Shock Relay output contact’s capacity, an auxiliary relay must be installed to prevent damage to the Shock Relay. The instruction manual included with each Shock Relay details how to add this auxiliary relay if required.